NEC Code Test — Questions and Answers
Question 1: A cord-and-plug-attached appliance is linked to a 25 ampere branch circuit. What is the maximum ampere rating that the appliance can handle?
- 20 amperes (Correct answer)
- 22.5 amperes
- 18.5 amperes
- 25 amperes
Correct answer: 20 amperes
According to NEC 210.23(A)(2), for branch circuits supplying two or more receptacles or outlets, the total cord-and-plug-connected load must not exceed 80% of the branch-circuit ampere rating. For a 25-ampere circuit, 80% of 25 A is 20 A. Therefore, the maximum ampere rating for a cord-and-plug-attached appliance connected to a 25-ampere branch circuit is 20 amperes.
Question 2: On a 15 amp branch circuit operating at 120 volts, what is the maximum number of receptacles that can be installed?
- 11
- 12
- 10 (Correct answer)
- 13
Correct answer: 10
The National Electrical Code (NEC) does not explicitly limit the number of receptacles on a general-purpose branch circuit. However, for planning purposes, especially in residential applications, a common guideline is to allocate 1.5 amperes (or 180 VA) per receptacle. For a 15-ampere, 120-volt circuit, the total capacity is 15 A * 120 V = 1800 VA. Dividing 1800 VA by 180 VA per receptacle yields 10 receptacles.
Question 3: The branch conductor's ampacity, which supplies power to the motor with an FLC of 25 amperes, is
- 28 amperes
- 30 amperes
- 25 amperes
- 32 amperes (Correct answer)
Correct answer: 32 amperes
According to NEC 430.22(A), the branch-circuit conductors supplying a single motor must have an ampacity not less than 125% of the motor's full-load current (FLC). For a motor with an FLC of 25 amperes, the required conductor ampacity would be 1.25 * 25 A = 31.25 A. The next standard conductor ampacity rating above 31.25 A is 32 amperes.
Question 4: A 2/0 THWN conductor is placed in a dry area at a temperature of 450 degrees Celsius. What is the conductor's corrected ampacity?
- 165 Amperes
- 170 Amperes (Correct answer)
- 175 Amperes
- 160 Amperes
Correct answer: 170 Amperes
Assuming the ambient temperature of '450 degrees Celsius' is a typo and meant '45 degrees Celsius' (as 450°C is far beyond conductor limits), we calculate the corrected ampacity. A 2/0 AWG THWN conductor is often dual-rated as THHN/THWN, allowing for a 90°C ampacity of 195 A (from NEC Table 310.16). Applying the temperature correction factor for 45°C from the 90°C column (Table 310.15(B)(2)(a)), which is 0.87, results in 195 A * 0.87 = 169.65 A, which rounds to 170 Amperes.
Question 5: A 1/0 THWN in a wet location has a rated ampacity of 150 amperes. If the same conductor is used at a temperature of 400 degrees Celsius. What is the corrected ampacity?
- 142 amperes
- 138 amperes
- 132 amperes (Correct answer)
- 150 amperes
Correct answer: 132 amperes
Temperature correction factor of 1/0 THWN Conductor for 40-750 C = 0.88 The corrected ampacity = 0.88 * 150 = 132 amperes
Question 6: The entry points of underground ducts or conduits into the building must be sealed.
- True (Correct answer)
- False
Correct answer: True
These must be sealed to prevent the entry of gases or moisture in to the building.
Question 7: If the raceway contains four 1/0 THWN conductors, what is the ampacity of a 1/0 THWN conductor in a dry location at a temperature of 1040 F?
- 132
- 124 (Correct answer)
- 165
- 170
Correct answer: 124
The conductor ampacity of 1/0 THWN in dry location ( 900C) = 170 amperes ( NEC Table 310.15(B)(16)) Ambient temperature correction factor at 1080F = 0.91 ( NEC Table 310.15(B)(2)) Raceway conductor bundle adjustment factor for 4 conductors = 0.8 ( NEC Table 310.15(B)(3)(a)) corrected ampacity = 170 * 0.8*0.91 = 124 amperes
Question 8: What conductor size is needed for a single-family housing unit with an estimated load of 220 amps and a maximum unbalanced neutral load of 110 amps?
- 3/0 AWG and 3 AWG (Correct answer)
- 3/0 AWG and 2 AWG
- 2/0 AWG and 2 AWG
- 1/0 AWG and 4 AWG
Correct answer: 3/0 AWG and 3 AWG
Service conductor for 225 Amperes load = 3/0 AWG neutral conductor for unbalanced load 110 = 3 AWG
Question 9: Which of the following is the minimum size of a single supply-side bonding jumper for three metal raceways with 300 kcmil service conductors each?
- 1 AWG
- 3 AWG
- 1/0 AWG
- 2 AWG (Correct answer)
Correct answer: 2 AWG
NEC Table 250.102(C)(1) For over 3/0 AWG and 350 kcmil the required bonding jumper size is 2 AWG
Question 10: The connected load of a single family dwelling unit is 4000 VA. The calculated demand load is which of the following?
- 4000 VA
- 3350 VA (Correct answer)
- 3550 VA
- 3850 VA
Correct answer: 3350 VA
First 3000 VA the demand factor is 100% = 3000 * 100 % = 3000 VA remaining (4000-3000) = 1000 ( demand factor = 35%) = 1000 * 0.35 = 350 VA total demand load = 3000 + 350 = 3350 VA
Question 11: What is the adjustment ampacity of a 3/0 THWN conductor in a wet location with an ambient temperature of 1080F? There are four 3/0 THWN conductors in the raceway.
- 153 amperes
- 133 amperes
- 119 amperes (Correct answer)
- 144 amperes
Correct answer: 119 amperes
3/0 THWN conductor ampacity in wet location (750C) = 175 Amperes ( NEC 310.15(B)(16)) Ambient temperature correction factor at 1080F = 0.85 ( NEC 310.15(B)(2)) raceway conductor bundle adjustment factor for 4 conductors= 0.8 ( NEC 310.15(B)(3)(a)) The conductor ampacity = 175 * 0.85 * 0.8 = 119 Amperes
Question 12: The voltmeter at one end of the feeder reads 240 volts. What is the volt-minimum meter's reading voltage at the outlet of lighting loads?
- 240 volts
- 228 volts
- 232.8 volts (Correct answer)
- 235 volts
Correct answer: 232.8 volts
The maximum voltage drop in feeder is 3 % the voltmeter reading = 240 – 0.03 * 240 = 240 – 7.2 = 232.8 volts
Question 13: The capacity of the conductor is 150 amperes. If five conductors are placed in a flexible cord, what is the maximum conductor ampacity allowed for each conductor?
- 135 amperes
- 105 amperes
- 140 ampere
- 120 amperes (Correct answer)
Correct answer: 120 amperes
For 5 conductors in flexible cord allowed ampacity percentage = 80 % of rated amapcity Allowed amapcity of each conductor with 150 Ampere rating = 150 * 0.8 = 120 amperes.
Question 14: For a 4200 W, 240 V electric water heater connected in a building, what is the maximum size over current device required?
- 25 A
- 30 A (Correct answer)
- 35 A
- 40 A
Correct answer: 30 A
Protection rating for an electric water heater should be less than 150% of the rating of device. Protection size = 4200 / 240 * 1.5 Protections size = 26.25 A The nearest next size over current device is 30 A.
Question 15: In a 3/4 EMT trade size, how many 10 AWG RHH conductors may be installed?
- 8 conductors
- 3 conductors
- 5 conductors
- 6 conductors (Correct answer)
Correct answer: 6 conductors
Total 6 10 AWG RHH conductors can be installed in trade size ¾ EMT.
Question 16: What size service conductors are needed for a 190 A calculated load in a dwelling? The service disconnect breaker has a 200-amp rating.
- 2/0 AWG (Correct answer)
- 1/0 AWG
- 4/0 AWG
- 3/0 AWG
Correct answer: 2/0 AWG
Answer : 2/0 AWG Note : Service conductors that supply individual dwelling unit or single dwelling unit can have ampacity rating of 83% of service disconnect. The conductor ampacity for 200 A service disconnect = 0.83 * 200 = 166 amperes Refer : NEC Table 310.15(B)(16) 2/0 AWG with ampacity 175 amperes ( 750 C) is suitable as service conductor
A cord-and-plug-attached appliance is linked to a 25 ampere branch circuit.
What is the maximum ampere rating that the appliance can handle?
What Practice Test Geeks adds beyond an AI chat for NEC
An AI chatbot can quiz you, but it can't reproduce the exam conditions or keep your record. Here you get:
- A timed, full-length NEC mock exam — 80 questions in 240 minutes with a 70% pass mark, modeled on the official exam's question count and time limit, followed by a score report broken down by exam domain.
- A fixed NEC question bank: the same test every attempt, so your score is comparable from one try to the next instead of changing with every regenerated quiz.
- Progress saved on your device: completed tests, scores and missed questions stay in My Progress, so you can retake only what you got wrong.
- A printable NEC cheat sheet you can print or save as a PDF.
- NEC flashcards built from the same question bank.