โ† All IEC Flashcard Decks

Grounding and Bonding Flashcards

6 cards from real IEC practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 6 Grounding and Bonding flashcards as text
  1. What is the primary purpose of bonding in an electrical system according to NEC Article 250?

    Answer: To ensure all metallic components are at the same electrical potential, creating a low-impedance path for fault current.

    Bonding connects all non-current-carrying metallic parts of an electrical system to create a continuous, low-impedance path. This path is crucial for allowing enough fault current to flow to trip the overcurrent protection device (like a circuit breaker) quickly, preventing metal parts from becoming dangerously energized.

  2. An electrician is installing a service for a new commercial building. Which of the following is an essential component for connecting the grounded conductor and the equipment grounding conductor to the service enclosure?

    Answer: A main bonding jumper

    The National Electrical Code (NEC) requires a main bonding jumper at the service to connect the grounded conductor (neutral) to the equipment grounding conductor(s) and the service disconnect enclosure. This connection establishes the effective ground-fault current path.

  3. Which of the following is NOT a primary function of an Equipment Grounding Conductor (EGC)?

    Answer: To carry the unbalanced neutral current during normal circuit operation.

    The Equipment Grounding Conductor (EGC) is a safety conductor and should only carry current during a ground-fault condition. The grounded conductor (neutral) is the conductor designed to carry the unbalanced current in a circuit during normal operation.

  4. In a new installation, a single ground rod is driven 8 feet into the earth. A resistance measurement shows 40 ohms. According to the NEC, what is the required next step?

    Answer: Install a second ground rod, spaced at least 6 feet away, and bond it to the first.

    NEC Section 250.53(A)(2) states that if a single rod, pipe, or plate electrode has a resistance to earth of 25 ohms or more, it must be supplemented by an additional electrode. For rod electrodes, the supplemental rod must be installed no less than 6 feet from the first.

  5. When installing a feeder to a detached garage with its own subpanel, which practice is critical for safety?

    Answer: Running a separate equipment grounding conductor from the main panel and keeping the neutral and ground bars isolated in the subpanel.

    In a subpanel located in a separate building, the grounded (neutral) conductor and the equipment grounding conductor must be kept separate. A separate equipment grounding conductor must be run with the feeder conductors to provide the effective ground-fault current path back to the main service. Bonding the neutral and ground at the subpanel would create objectionable current on the grounding conductors. A grounding electrode system is also required at the detached structure.

  6. According to NEC Article 250, which of the following can be used as a grounding electrode?

    Answer: A concrete-encased electrode (Ufer ground) consisting of at least 20 feet of 1/2-inch rebar.

    NEC Section 250.52(A)(3) permits a concrete-encased electrode, consisting of at least 20 feet of either bare copper conductor (not smaller than 4 AWG) or one or more bare or zinc-galvanized or other electrically conductive coated steel reinforcing bars of not less than 1/2 inch in diameter, to be used as a grounding electrode. Metal underground gas piping is explicitly forbidden, and rebar must be at least 20 feet long.