F89 Fire Code Compliance Questions and Answers 1 — Questions and Answers
Question 1: An FLSD notices that the Fire Department Connection (FDC) for the building's standpipe system is not visible from the street. According to NYC Fire Code, what is required in this situation?
- A sign with red letters on a white background must be posted on the FDC itself.
- An approved sign with letters 'FDC' at least 10 inches high must be mounted on the street front, with an arrow indicating the location. (Correct answer)
- A continuous green light must be installed above the FDC to increase visibility at night.
- The FLSD must file for a variance with the FDNY, as relocating the FDC is the only acceptable solution.
Correct answer: An approved sign with letters 'FDC' at least 10 inches high must be mounted on the street front, with an arrow indicating the location.
When a Fire Department Connection is not visible from the street, the NYC Fire Code and related standards require an approved sign to be placed on the street-facing side of the building to direct the arriving fire department. This sign must have letters 'FDC' that are a minimum of 10 inches high and include an arrow to point towards the connection's location.
Question 2: During a routine tour, an FLSD discovers that hot work (welding) is being performed on the roof without proper authorization. What is a critical immediate action the FLSD must take?
- Tell the workers to be more careful and to post a fire guard.
- Issue a verbal warning and document the infraction in the FLS Log Book.
- Immediately stop the work and verify that a valid FDNY permit and a pre-hot work check have been completed. (Correct answer)
- Wait until the workers are finished and then report the incident to the building manager.
Correct answer: Immediately stop the work and verify that a valid FDNY permit and a pre-hot work check have been completed.
Hot work, such as welding, presents a significant fire hazard and is strictly regulated. The FLSD's primary responsibility upon discovering unauthorized hot work is to stop the operation immediately to prevent a potential fire. They must then confirm that all safety protocols, including obtaining a valid permit and conducting a pre-hot work check by a responsible person, have been followed before work can safely resume.
Question 3: What is the function of Phase I Emergency Recall Operation for an elevator during a fire alarm activation?
- It allows building occupants to use the elevator for evacuation for a period of 5 minutes.
- It sends the elevator car to the roof for firefighter access.
- It allows firefighters to manually control the elevator from inside the car.
- It automatically returns the elevator car to a designated recall level, typically the lobby, and removes it from normal service. (Correct answer)
Correct answer: It automatically returns the elevator car to a designated recall level, typically the lobby, and removes it from normal service.
Phase I Emergency Recall is a critical life safety feature that, upon activation by a fire alarm initiating device (like a smoke detector in an elevator lobby), automatically recalls the elevator car to a designated level, usually the ground floor lobby. This action prevents occupants from using a potentially unsafe elevator and makes it available for FDNY use. Phase II is the in-car operation used by firefighters.
Question 4: Which of the following alarm signals at the Fire Command Center indicates a condition that could prevent a fire protection system from operating correctly, such as a closed sprinkler control valve?
- A Fire Alarm signal
- A Trouble signal
- A Supervisory signal (Correct answer)
- A Phase II signal
Correct answer: A Supervisory signal
A Supervisory signal indicates that a system or device is in an off-normal state that could adversely affect its performance, but it is not an active fire or system fault. A common example is a tamper switch on a sprinkler control valve, which sends a supervisory signal if the valve is not in the fully open position. A trouble signal typically indicates a fault in the wiring or components of the alarm system itself.
Question 5: In a high-rise office building, a fire alarm system that includes both automatic fire detection and a two-way voice communication system for issuing instructions to occupants is classified as which type of system?
- Class A System
- Class B System
- Class J System
- Class E System (Correct answer)
Correct answer: Class E System
A Class E fire alarm system is the designation used in the NYC Fire Code for systems found in high-rise office buildings. These systems are required to feature, among other things, automatic smoke detection, manual pull stations, alarm signals, and a two-way voice communication capability to allow the FLSD and FDNY to provide instructions to occupants during an emergency.
Question 6: An FLSD is reviewing the required signage for the elevator cars in their building. A sign located in or near every elevator car must state which of the following?
- "In case of fire, use elevator to evacuate."
- "Elevator capacity: 15 persons."
- "In fire emergency, do not use elevator. Use the exit stairs." (Correct answer)
- "This elevator is for freight use only during emergencies."
Correct answer: "In fire emergency, do not use elevator. Use the exit stairs."
The NYC Building Code requires specific emergency signage in elevators to ensure occupant safety. A key requirement is a sign that clearly instructs occupants NOT to use the elevator during a fire emergency and to use the exit stairs instead. This is because elevators can malfunction, open on a fire floor, or become a trap during a fire.
An FLSD notices that the Fire Department Connection (FDC) for the building's standpipe system is not visible from the street.
According to NYC Fire Code, what is required in this situation?
What Practice Test Geeks adds beyond an AI chat for F89
An AI chatbot can quiz you, but it can't reproduce the exam conditions or keep your record. Here you get:
- A timed, full-length F89 mock exam — 55 questions in 83 minutes with a 70% pass mark, modeled on the official exam's question count and time limit, followed by a score report broken down by exam domain.
- A fixed F89 question bank: the same test every attempt, so your score is comparable from one try to the next instead of changing with every regenerated quiz.
- Progress saved on your device: completed tests, scores and missed questions stay in My Progress, so you can retake only what you got wrong.
- A printable F89 cheat sheet you can print or save as a PDF.
- F89 flashcards built from the same question bank.